6. Diagrams
6.2 Battery and Breaker Diagrams
6.2.1 192 VDC (Single-Phase)
192 VDC
Notes:
• All internal wiring is UL-listed, MTW, 105C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 50 A, 600 VDC, 42 KAIC.
• Cabinets with breakers are shipped with the breaker in the off/open position and one of the jumper cables disconnected.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
218 VDC
218 VDC
(Charger adjusted and tested to 216-221 VDC at float)
16