Installation Conditions - Siemens Milltronics Multiranger 100 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 43
Specifications
For a complete listing, see the MultiRanger Instruction manual. For Approval information, please refer to
the MultiRanger nameplate.
Power
AC Version
• 100-230 V AC ± 15%, 50 / 60 Hz, 36 VA (17W)
• fuse: F3: 2 AG, Slow Blow, 0.375A, 250V
1.
Power consumption is listed at maximum.

Installation Conditions

Altitude
• 2000m max
Pollution Degree
• 4
Outputs
Transducer Drive
• 315 V peak
Control Relays
• 2 or 4 Form A, NO
relays (relays
numbered 1, 2, 4, 5)
1.
All relays are certified only for use with equipment that fails in a state at or under the rated maximums of relays.
Inputs
mA (analog) (1) [MR 200 only]
• 0-20 or 4-20 mA, from alternate
device, scalable
Transducers
Compatible
• Echomax series
• STH series
• (44 kHz)
Page EN-2
Ambient Temperature
• -20 to 50 °C (-5 to 122 °F)
Range
• 0.3 m (1 ft) to 15 m (50 ft),
transducer dependent
mA Analog
• 0-20 mA
• 4-20 mA
• 750 ohm maximum
• Resolution of 0.1%
Alarm/Control Relays
• 1 or 2 Form C, NO, or NC
relay (relays numbered
3, 6)
Discrete (2)
• 10-50 V dc switching level
• logical 0 = < 0.5 V DC
Cable (365m Max)
• do not use coaxial cable for transducers
• 2-3 copper conductors, twisted with shield, drain wire, 300Vrms,
2
0.5mm
(22-18AWG), nominal capacitance between adjacent
conductors @ 1 kHz = 19pF/ft., nominal capacitance between
conductor and shield @ 1kHz = 33 pF/ft. (Belden 8760 is acceptable).
MultiRanger – QUICK START MANUAL
DC Version
1
1
• 12-30 V DC, 20W
• fuse: F3: 2 AG, Slow Blow, 2A, 250V
Installation Category
• II
Relays
• Three: 2 control, 1 alarm control
• Six: 4 control, 2 alarm control
• all relays rated 5 A at 250 V AC,
non-inductive
Communication
• RS-232 (Modbus RTU and ASCII
via RJ-11 connector)
• RS-485 (Modbus RTU) via
terminal blocks
1
• logical 1 = 10 to 50 V DC
• 3 mA maximum draw
7ML19981QD82

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Milltronics multiranger 200

Tabla de contenido