Descargar Imprimir esta página

Publicidad

Enlaces rápidos

WARNINGS AND CAUTIONS
TO AVOID FIRE, SHOCK OR DEATH, TURN OFF POWER at circuit breaker or fuse and
test that the power is off before wiring!
To be installed and/or used in accordance with electrical codes and regulations.
If you are not sure about any part of these instructions, consult an electrician.
Features
• Intermateable and compatible with competitive same nose cam-type products - can be
retrofitted to existing locations and power distribution systems
• Shatter and crack proof - high durometer rubber sleeve
• Color coded insulating sleeves - fast and easy phase identification
• Self-compensating for wear - slit and cam in male contact provide spring action for longer usage
• Fast connect/disconnect - twist and pull double cam/guide boss design
• High conductivity - positive, vibration proof connection provided by double cam design
• Wide variety of applications - usable with a wide range of cable sizes and amperage ratings
Hardware Required ( not supplied )
TERMINATION
Threaded stud
• Listed Compression Lug
• 1/2 in. Flat Washer
• 1/2-13 in. UNC Hex Nut (5/16 in. thickness)
• 1/2 in. Lock Washer
Installation
NOTE: Use the Maximum Device Rating Table to select the correct cable size for the application.
Panel Cutout ( not to scale )
3.50 in.
[88.9 mm]
BOLT HOLE
PATTERN
0.08 in.
[1.9 mm]
C L
BOLT
HOLES
2.88 in.
[73 mm]
2.48 in.
[62.9 mm]
SQ.
Panel Receptacle
1/4-20 in. Bolts (4)
Align, push together and twist.
Male Connector
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire
(Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for two years from the
purchase date. Leviton's only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal
of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration
of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage
to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
17 Series Taper Nose Panel Receptacles
Rated 600V, up to 600A continuous current
22 Series Ball Nose and 23 Series Taper Nose Panel Receptacles
Rated: 600V, up to 690A continuous current
MOUNTING
Panel Receptacles
• 1/4-20 in. Bolts (4)
• 1/4-20 in. Lock Washers (4)
• 1/4-20 in. Nuts (4)
0.28 in.
[7.1 mm]
(4PL)
Installation
1/4-20 in.
Lock Washers (4)
1/4-20 in. Nuts (4)
Panel Cutout
Panel Front
Connect
Panel
Female Panel Receptacle
LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com
Cable Size: 350 - 500 MCM
Cable Size: 250 - 750 MCM
WARNINGS AND CAUTIONS
Use copper cable only. Do not exceed 600A for 17 Series and do not exceed 690A for 22
and 23 Series. Acceptable cable types include: DLO, W, & P.
Female contacts for taper nose and ball nose devices are not interchangeable.
Taper nose assemblies will not mate properly with ball nose assemblies.
INSTALLATION INSTRUCTIONS
Cable Size MCM
Panel Receptacle
* NOTE: For 22 and 23 Series Connectors,
depress button on sleeve, untwist and pull apart.
MAXIMUM DEVICE RATING
Max Device Rating
90° C Cable
250
445A
262
445A
313
445A
350
500A
373
500A
444
500A
500
600A
535
600A
646
600A
750
690A
777
690A
Wiring
1/2 in. Lock Washer
1/2 in. Diameter Washer
Listed Compression Lug to
suit cable size. Ensure lug
is positioned with sufficient
clearance from mounting bolts.
Panel
Back
Prepare cable end and insert and crimp cable
into lug per manufacturer's requirements
Disconnect
* Depress Button
Panel
PK-A3187-10-02-0B
English
Series
22/23
22/23
22/23
17/22/23
17/22/23
17/22/23
17/22/23
22/23
22/23
22/23
22/23
1/2-13 UNC
Hex Nut
- 5/16 in. thickness
(Tighten nut to
35 ft-lbs.maximum)

Publicidad

loading

Resumen de contenidos para Leviton 17 Serie

  • Página 1 Leviton warrants to the original consumer purchaser and not for the benefit...
  • Página 2 (0.08 pulgadas) au moment de sa vente par Leviton, et n’en présentera pas tant qu’il est utilisé de façon normale et adéquate, pendant une période de 2 ans suivant la date d’achat. La seule obligation de Leviton sera de corriger les dits défauts en réparant ou en remplaçant le produit défectueux si ce dernier est retourné...