Electric control box
PFC-T
OPERATING INSTRUCTION
Index
1.
Type
2.
Operating conditions
3.
Constuction
3.1.
4.
5.
6.
6.1.
7.
8.
8.1.
9.
10.
Outside of box cover
11.
Inside of the box
12.
Declaration of conformity
1. Type
Type
PFC-T 11
PFC-T 16
PFC - T 11
Maximum current 11A
Three-phase power
PFC series (Power Factor Control)
max. current
output
A
11
16
2. Operating conditions
- Power supply 380/400V ±10% 50-60 Hz
- Rated insulation voltage: 690 Vac
- Maximum thermal protection: 8A/11A/16A
- Rated short-time withstand current: 1,5 kA
- Rated conditional short-circuit current: 1 kA
- Free voltage contact ratings: 240Vac, 1A max.
- Environment: B
- Ambient temperature: -5 °C +40 °C
- Relative humidity: from 20% to 90% without
condensation
- Protection IP55
- Case side 315x235x170, weight 1.8 kg.
- Standards: IEC/EN 60439-1
3. Constuction
Control unit for a three-phase submersible pump.
Functions are controlled from the PFC-T
electronic control panel, which reads the power
factor (PF) for protection against dry functions,
without installing the level probe in the well.
The PFC-T control unit also detects the phase
failure and the sequence of phases in the power
line and enables setting:
- The motor rated power
- The PF alarm limit
- The minimum and maximum limits for power
voltage
- Programming 4 restarts for the pump when there
is no water
- The pump working times and the stops if there is
no air in the tank (patented system).
Materials
- Thermoplastic case
- Door lock master switch:
- Power line fuses
- Auxiliary circuit fuse
- Starting contactor
- Transformer
- PFC-T electronic control panel with display and
microprocessor
- Terminals for connecting the power line
- Terminals for connecting pressure switch or float
switch
- Terminals for connecting the RA 100 remote
alarm panel
- Cable glands
7