KAL790 Addressable Retention Module
Installation Sheet
EN ES
IT
PT FR NL CS NO PL HU
1
EN: Installation instructions
Description
The KAL790 provides a remote input and a potential-free
voltage relay output to an addressable fire detection system.
The input signal is constantly monitored and its status
communicated to the fire panel. The output is fail-to-safe.
Auxiliary supply monitoring is also included.
The output has three positions: common (C), normally open
(NO) and normally closed (NC). In standby the C and NC
contacts are connected. When the output is activated the C
contact is connected to the NO contact.
The input is polarity insensitive. When electrical contacts are
not connected, the module remains in standby mode.
© 2020 Carrier. All rights reserved.
Note:
The input state is latched (this is not configurable) and
returns to standby after a system reset.
The module may be used with any device and the choice of
contact used (C, NC or NO) will set the desired event.
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN 54:14 standard and local regulations.
Module installation
Disconnect the fire system power supply and install the module
in the protective housing provided.
Connect the loop cable shield wire to the earth screw.
1 / 20
P/N 10-5151-501-101-02 • ISS 15JUN20