The 24 V power supply for the module can be taken from the
loop or from an auxiliary power source.
If 10 or more KAL700 modules are connected to the loop an
auxiliary power source should be used.
Connection
The module connectors, DIP switch, and status LED are
shown in Figure 1:
1.
Earth screw
2.
Loop connectors
3.
Auxiliary power supply connectors
4.
Relay connectors (C, NC, NO)
5.
Input connectors
6.
DIP switch
7.
Status LED
Loop overloading
Always verify large installations using a loop load calculator to
confirm that enough power is available on the loop.
Note:
To avoid loop overloading when using loop-powered
devices, see the system installation and configuration
guidelines in the Loop Power and I/O Modules Application
Note. This document is available from your local distributor.
Power supply configuration
To set the module power supply, remove the unit cover and
configure jumpers JMP1 and JMP2.
Loop powered jumper
configuration.
WARNING:
Do not connect a 24 VDC auxiliary power supply
to the module if power is supplied by the loop
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status LED is configured using DIP switch 8:
If set to ON the LED will flash during all communications
between the module and the control panel.
If set to OFF it will flash only during selected
communications between the module and control panel
(see control panel manual for further details).
The status LED is lit constantly during alarm.

Maintenance and testing

Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
2 / 20
24 VDC auxiliary power supply
jumper configuration.
To test the module:
1.
Activate the input signal and check the activation message
at the control panel.
2.
Activate the relay from the control panel and check the
module relay changes position.
3.
If the status LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
Specifications
Operating voltage
Relay contact rating
Max.switching voltage
Nominal current
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions
Current consumption (externally powered)
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
Current consumption
24 VDC aux. supply (standby)
24 VDC aux. supply (alarm)
Current consumption (loop powered)
Loop current consumption
Standby
Alarm

Regulatory information

This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
Declaration of Performance
number
Year of first CE marking
Product identification
Intended use
Declared performance
Manufacturer
P/N 10-5151-501-101-02 • ISS • 15JUN20
22 to 38 VDC
AC: 42 V peak / DC: 30 V
AC: 0.5 A / DC: 0.5 A
−10 to +50ºC
−10 to +70ºC
10 to 95% (noncondensing)
370 g
182 × 142 × 77 mm
110 µA
135 µA
10 mA
200 µA
<50 mA
350 µA
<3.4 mA
0370
360-4109-1299
08
KAL790
See the product Declaration of
Performance
See the product Declaration of
Performance
UTC CCS Manufacturing Polska Sp.
Z o.o. Ul. Kolejowa 24. 39-100
Ropczyce, Poland
Authorized EU manufacturing
representative: UTC Fire & Security
B.V. Kelvinstraat 7, 6003 DH Weert,
Netherlands