Using a fork spanner SW 27 screw the union
►
nuts SW 30 (3) and the screw-in fittings to-
gether M 27 (1) (tightening torque 30 Nm).
In doing so, alternatingly tighten just 1–2
turns in each case to prevent the threaded
connection part from jamming.
Attach panels (4).
►
Transport radiator only in a standing posi-
►
tion.
Install built-into-wall brackets (see Fig. 1–8)
Observe submersible radiator-wall spacing
►
(WA) (see Fig. C).
In the event of a projection from the wall,
e.g. insulation material, the projecting
length of the built-into-wall bracket is re-
duced by the thickness of the projection (see
Fig. 4).
Prepare tools.
►
Drill holes. Note walling material.
►
Note: Brackets with lift restraints are installed
on top, outside and possibly additionally even-
ly spaced along the length.
Pre-install lift restraints.
►
Install built-into-wall brackets:
►
Note the orientation of the built-into-
–
wall bracket, slit to the top.
Make sure that the built-into-wall brack-
–
et's expansion zone is not completely
within a hollow space of the building
material used.
Align and secure the built-into-wall brack-
►
ets.
Shorten panel if required and attach with
►
the raw edge to the wall.
Attach rosette.
►
Install clamp (see Fig. 9–14).
Pre-install clamp.
►
►
Turn traverse holder by 90°.
Attach clamp on the radiator from behind
►
and from the front turn the traverse holder
back by 90°.
Align clamp and tighten (tightening torque
►
7 Nm).
Attach cover cap.
►
For BH 1050: Install spacers (see Fig. 15–16).
Depending on the installation situation,
►
shorten the spacer and apply the long or
short nut.
6
Installing and securing the radiator (see
Fig. 17–19)
►
Place the radiator with the straps into the
brackets and align laterally.
►
Clamp the lift restraints over the radiator
straps.
Align radiator.
►
Standard version connection
Vent plugs (top) and blind plugs are factory
pre-assembled.
Unscrew painted blind plugs at the desig-
►
nated connection points.
Connect radiator with commercially avail-
►
able fittings upstream.
Tightly cap open connections with vent
►
plugs (top) and blind plugs.
Connection version with built-in valve
Valve with factory pre-set k
facturer's data).
Vent plugs (top) and blind plugs are factory
pre-assembled.
Remove painted caps on the valve mount-
►
ings and dispose of, as they must not be
used as seals on the radiator.
Connect radiator with commercially avail-
►
able fittings upstream on the valve mount-
ings.
Special connections
See manufacturer's data.
►
Commissioning
Remove protective packaging completely
►
during final cleaning or prior to commis-
sioning.
Fill the radiator and evacuate the air from it
►
via the air vent. Risk of scalding!
Check radiator and connections for leaks.
►
value (see manu-