6. Service Function
Pressing the "Reset/Test/Service" button (5 - Fig. 1) for 10 seconds will disengage all alarm functions
for 60 minutes. During this period, it is always possible to start a new 60-minutes period by pressing
the button for 10 seconds again. Return to active status happens automatically at the end of the
60-minutes period or may be done manually by a single press on the "Reset/Test/Service"-button.
When the service function is activated all LEDs will flash and all relays will be in normal mode position.
See Fig. 4.
7. Sound, light & MUTE button
"MUTE" button (9 - Fig. 1) mutes the buzzer for 60 minutes. If gas concentration drops beneath
A-level alarm buzzer (7 - Fig. 1) is deactivated and if gas concentration drops beneath B-level alarm
LED (8 - Fig. 1) is deactivated. For more details see Fig. 2 (10).
8. Manual activation of all alarm levels
Closed contact/loop gives full sensor signal resulting in all alarm levels getting activated (11 - Fig. 1).
9. Installation
The LDM150R Remote Sensor is connected to the terminals on the main PCB-board (6 - Fig. 1).
See the wiring diagram in Fig. 1.
10. Annual Function Control
Testing the system is recommended to be done at least once a year. A basic function test can be
made using the MCT150 Monitor Calibration Tool.
11. Automatic/Manual Alarm Reset
Is managed by DIP switch (1 - Fig. 1) n
manual reset by pressing the "Reset/Test/Service" button (5 - Fig. 1 - located under the lid).
12. Alarm Time Delay
Is managed by DIP-switches (1 - Fig. 1) n
n
1
n
2
o
o
ON
ON
No alarm delay
OFF
ON
(1) minutes alarm delay
ON
OFF
(10) minutes alarm delay
OFF
OFF
(30) minutes alarm delay
13. Self-Test Function
Press the "Reset/Test/Service" button (5 - Fig. 1) for 5 seconds and the test program will start and
check through all LED and all relay functions in five seconds intervals. See Fig. 3.
743-203-xxx LDM150R Operating Manual 200305
3 where "ON" means automatic reset and "OFF" means
o
1 and n
o
Alarm delay (T1)
2:
o