3. Cautions and Warnings

WARNING
The unit must be opened by authorized personnel only!
No matter if power supply is removed the unit can still have external high voltage
over the relay contacts.

4. Alarm Levels, Factory Settings

Default factory settings:
Ammonia (NH
) 0-4000 ppm
3
HFC, HFO, HCFC 0-4000 ppm
Carbon Dioxide (CO
) 0-10000 ppm
2
SETTING ALARM LEVELS (THRESHOLDS)
The monitoring unit is delivered with default alarm settings as standard.
Settings depend on detector type and are made using the MCT150 Monitor
Calibration Tool. MCT150 is to be connected to the test terminal (3 - Fig. 1).
743-203-xxx LDM150R Operating Manual 200305
C=150 ppm
B=500 ppm
C=100 ppm
B=1000 ppm
C=2000 ppm
B=5000 ppm
A=3000 ppm
A=2000 ppm
A=8000 ppm
8/48