14. Fault Function
If there is a voltage drop (GV-value below 0,1V) from the sensor there is a fault situation. During the
first four hours the green LED will be deactivated, and the other LEDs will flash. Alarm relay C will
change state. After four hours the LED "Alarm B" will light (other LED's will be deactivated) and relay
"Alarm B" will also change state.
15. Fail Safe
Relays are in normal mode energized and will change state in case of power failure or a fault.
16. Technical Data
Housing:
Power consumption:
Power supply:
Indications:
Outputs relay:
Ambient temp:
Humidity:
Glands:
Screw terminals:
Please Note!
The semi conductive sensors used in the LDM150R range of products are not gas
specific. Care should be taken when installing the equipment to minimize any cross
contamination from other gases or vapors.
For further guidance on specific applications contact us.
This product is intended for use in the industrial area.
Specifications subject to change.
11/48
Polycarbonate, (PC) IP67
Max 3W
LDM150R: 12-24V AC/DC
LDM150R,High Voltage: 230V AC, 50/60 Hz
Power/Active and alarm indication on three levels.
Potential free contacts (230V, max 5A)
-40 °C - + 50 C (Automatic temperature compensation)
0-95% RH (non-condensing)
5 x M16 membrane glands
< 1,5 mm
, fuse, max. 10A
2
743-203-xxx LDM150R Operating Manual 200305