EN: Installation Sheet

Description
This document includes installation information for the
following IO2000C series I/O modules:
IO2014C (4 inputs)
IO2031C (2 inputs / 1 output)
IO2032C (2 inputs / 2 outputs)
IO2034C (4 inputs / 4 outputs)
Available inputs and outputs
The available inputs and outputs for each module are indicated
with a cross in the following table:
Table 1: Available inputs and outputs
Module
Inputs
A
B
C
IO2014C
X
X
X
IO2031C
X
X
IO2032C
X
X
IO2034C
X
X
X
Installation
Module layout
Figure 2 shows:
1.
Fault LED for open or short circuit on supervised inputs
2.
Rotary dials for module addressing
3.
COM2 supply voltage input (positive)
4.
COM1 supply voltage input (negative
5.
Inputs A to D
6.
Outputs A to D (NC, C, NO)
Assembly
Install the module into the protective housing as shown in
Figure 1. Connecting cables should be fed through the cable
entry hole at the rear of the protective housing before the
module is fixed into place.
2 / 16
Outputs
D
A
B
C
D
X
X
X
X
X
X
X
X
X
4
Wiring
Connect the I/O module to the loop via the COM2 (positive)
and COM1 (negative) inputs.
Inputs A to D each require an end-of-line resistor (150KΩ, 5%,
1/4W). Inputs are supervised for open circuit (ON/OFF) or
short circuit (ON/OFF) status. For a fully supervised input
(open and short circuit) an additional resistor (33KΩ, 5%,
1/4W) must be installed as shown in Figure 3.
Table 2: Impedance and device state
Input loop impedance*
Open circuit - 555KΩ
243KΩ - 54KΩ
39KΩ – 11KΩ
5.6KΩ – short circuit
* 150KΩ EOL included
Addressing
Each module must be assigned an address from 1 to 128. Use
the rotary dial marked 0 to 12 to set the tens and hundreds part
of the address, and the rotary dial marked 0 to 9 for the
remaining digits. See Figure 4 for sample address settings.
Note:
To overcome the mechanical effects of shipping and
storage, we recommend that you first rotate each dial counter-
clockwise (to the 0 position) and then clockwise (to the dial's
maximum position) before setting the required address.
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Operating voltage
Current consumption (in standby):
IO2014C / IO2034C max.
IO2014C / IO2034C typical
IO2031C / IO2032C max.
IO2031C / IO2032C typical
Line resistance
End-of-line resistor
8
112
Device state
Open (open circuit)
Passive (contact open)
Active (contact closed)
Short (short circuit)
17 to 39 VDC
420 µA
350 µA
< 350 µA
< 300 µA
< 100Ω
150KΩ, 5%, 1/4W
P/N 55370161 • REV 05 • ISS 30OCT13