PROBLEM
The automation fails to turn on
Only the control panel fails to turn on
The leaf moves in the opposite direc-
tion
The door does not open
The door does not close
The photocell orange led is on
The flashing light is not working
Problem solving
POSSIBLE CAUSES
•
Mains power failure
•
Cut-out switch on OFF
8A fuse tripped
•
Connector C16M is not connected
•
•
2A fuse tripped
•
The motor phases are not con-
nected correctly
•
The limit switch FCA is pressed
The sensitive ridge and/or photo-
•
cell are in an alarm condition
•
The lock is locked
The limit switch FCC is pressed
•
•
The sensitive ridge and/or photo-
cell are in an alarm condition
•
Automatic closing is deactivated
(in the case of expecting auto-
matic closing
•
The lock is locked
•
There is an obstacle between the
photocell and the reflex reflector
or emitter
•
The photocell is not aligned cor-
rectly with the reflex reflector or
emitte
•
There is condensate in the reflex
reflector
•
Blown bulb
•
The flashing light is not connect-
ed
SOLUTION
•
Connect the mains
•
Move the cut-out switch to ON
Change the fuse
•
Connect connector C16M
•
•
Change the fuse
•
Invert the grey cable and the
brown cable inside the motor
•
Check the FCA and its adjustment
Check that there are no hindranc-
•
es to the safety devices
•
Open the lock
Check the FCC and its adjustment
•
•
Check that there are no hindranc-
es to the safety devices
•
Activate automatic closing from
the ZELIO PLC menu on the con-
trol panel
•
Open the lock
•
Remove the obstacle that is in-
terrupting the photocell beam
Check that the photocell is
•
aligned
throughout the door
stroke
Clean the reflex reflector
•
•
Change the 24V-25W bulb
•
Connect it through C10M