PROBLEM
The automation fails to turn on
Only the control panel fails to turn on
The leaf moves in the opposite direc-
tion
The door does not open
The door does not close
The photocell orange led is on
The flashing light is not working

Problem solving

POSSIBLE CAUSES
Mains power failure
Cut-out switch on OFF
8A fuse tripped
Connector C16M is not connected
2A fuse tripped
The motor phases are not con-
nected correctly
The limit switch FCA is pressed
The sensitive ridge and/or photo-
cell are in an alarm condition
The lock is locked
The limit switch FCC is pressed
The sensitive ridge and/or photo-
cell are in an alarm condition
Automatic closing is deactivated
(in the case of expecting auto-
matic closing
The lock is locked
There is an obstacle between the
photocell and the reflex reflector
or emitter
The photocell is not aligned cor-
rectly with the reflex reflector or
emitte
There is condensate in the reflex
reflector
Blown bulb
The flashing light is not connect-
ed
SOLUTION
Connect the mains
Move the cut-out switch to ON
Change the fuse
Connect connector C16M
Change the fuse
Invert the grey cable and the
brown cable inside the motor
Check the FCA and its adjustment
Check that there are no hindranc-
es to the safety devices
Open the lock
Check the FCC and its adjustment
Check that there are no hindranc-
es to the safety devices
Activate automatic closing from
the ZELIO PLC menu on the con-
trol panel
Open the lock
Remove the obstacle that is in-
terrupting the photocell beam
Check that the photocell is
aligned
throughout the door
stroke
Clean the reflex reflector
Change the 24V-25W bulb
Connect it through C10M
80