Initial Startup
To prepare the SITRANS LR260 for operation, complete the following steps:
1.
Set the desired language:
a)
Point the programmer at the display [from a maximum distance of 500 mm (1.6 ft)], then
press Right ARROW
b)
Press Up ARROW
parameter view.
c)
Press Right ARROW
d)
Scroll to the desired language and press Right ARROW
e)
Press Mode
2.
Set the device address (default = 126):
a)
In PROGRAM mode, navigate to: Level Meter > Communication > Device Address (5.1).
b)
Press RIGHT arrow
mode.
c)
If required, key in a new value and press RIGHT arrow
the new value.
d)
Press Mode
3.
Run the Quick Start Wizard via the handheld programmer (see below).
Quick Start Wizard via the handheld programmer
Notes:
• The Quick Start Wizard settings are inter-related and changes apply only after you click on
Yes in Apply? at the end of the Quick Start steps.
• Do not use the Quick Start wizard to modify individual parameters: see full parameter
listing in Instruction Manual (perform customization for your application only after the
Quick Start has been completed).
1. Quick Start
a)
Point the programmer at the display, then press Right ARROW
mode and open menu level 1.
b)
Press Right ARROW
c)
Press Right ARROW
values and move directly to the next item.
d)
To change a setting, scroll to the desired item or key in a new value.
e)
After modifying a value, press Right ARROW
to move to the next item.
f)
Quick Start settings take effect only after you select Yes to Apply changes in step 1.7.
A5E32114443
SITRANS LR260 (PROFIBUS PA) – QUICK START MANUAL
to activate PROGRAM mode and open menu level 1.
to scroll to Language (7.0) and Right ARROW
to enable Edit mode.
to return to Measurement mode.
, RIGHT arrow
to return to Measurement mode.
twice to navigate to menu item 1. 1 and open parameter view.
to open Edit mode or Down ARROW
to accept it.
, to open parameter view and enable Edit
to accept it. The LCD displays
to accept it and press Down ARROW
to open
to activate PROGRAM
to accept default
Page EN-13