For overfill protection:
1a
Install the device with the probe uncovered.
2a Power it up.
3a Set the first operating point for the switch, LRV at menu 0E
Set value for 0% (LRV): units must be pF (Menu 01 must read Pv = 0); probe must be
uncovered.
a
Turn the rotary switch to E (Empty).
b
Press both buttons and hold for about 1 second: the 0% point is now set.
(In FailSafe mode, the LCD blinks to indicate the probe is uncovered.)
4a Set the second switch point: use menu 0D to generate URV
Set value for 100% (URV): probe must be uncovered.
a
Turn the rotary switch to D (Delta Range).
b
Press and hold both buttons for about 1 second: this takes the minimum span and adds it
to the value for LRV to generate the value for URV. (This guarantees the device will
switch if the product approaches or touches the probe.)
c
If the device is over-sensitive, use the RED (+) button to increase the Delta Range
setting. (This will increase the value for URV and increase the span between LRV and
URV.)
(The LCD will stop blinking when the probe is covered.)
For dry-run (underfill) protection
1b Install the device with the probe covered.
2b Power it up.
3b Set the first operating point for the switch, URV at menu 0F
Set value for 100% (URV): units must be pF (Menu 01 must read Pv = 0); probe must be
covered.
a
Turn the rotary switch to F (Full).
b
Press both buttons and hold for about 1 second: the100% point is now set.
(The LCD stops blinking when the probe is covered.)
4b Set the second switch point: use menu 0D to generate LRV
Set value for 0% (URV): probe must be covered.
a
Turn the rotary switch to D (Delta Range).
b
Press both buttons and hold for about 1 second: this takes the minimum span and
subtracts it from the value for URV to generate the value for LRV.
c
For products that are conductive and viscous, use the RED (+) button to increase the
Delta Range setting. (This will decrease the value for LRV and increase the span
between URV and LRV).
(The LCD will blink if the probe is uncovered.)
In all cases:
5
View primary variable (PV): menu 00
Turn the rotary switch to 0. The LCD displays the actual pF reading.
6
Pointek CLS500 is now ready to operate.
Page EN-8
Quick Start Sequence
Pointek CLS500 – QUICK START MANUAL