eNgliSh
4.3 Walls
Distance to wall made of combustible material
- fig. 1
You may use the fireplace with an uninsulated flue pipe provided
the distances to walls made of combustible materials are as
shown in fig. 1.
Distance to walls covered by a firewall - fig.
1
Contact your local building authority regarding restrictions and
installation requirements.
Firewall requirement
The firewall must be at least 100 mm thick and be made of
brick, concrete-stone or light concrete. Other materials and
constructions with satisfactory documentation may also be used,
e.g. Jøtul Firepanel.
Distance to non combustible walls - fig. 1
By non combustible one means a non load-bearing wall of solid
brickwork/concrete.
4.4 Ceiling
There must be a minimum distance of 1000 mm to a combustible
ceiling above the fireplace.
4.5 Chimneys and flue pipes
•
The fireplace can be connected to a chimney and flue
pipe approved for solid fuel fired appliances with flue gas
temperatures specified in «2.0 Technical data.
•
The chimney's cross-section must be at least as big as the
flue pipe's cross-section. See «2.0 Technical data» when
calculating the correct chimney cross-section.
•
Several solid fuel fired appliances can be connected to the
same chimney if the chimney's cross-section is sufficient.
•
Connection to the chimney must be carried out in accordance
with the installation instructions from the supplier of the
chimney.
•
Before making a hole in the chimney the fireplace should be
test-mounted in order to correctly mark the position of the
fireplace and the hole in the chimney. See fig. 1 for minimum
dimensions.
•
Ensure that the flue pipe is inclined all the way up to the
chimney.
•
Use a flue pipe bend with a sweeping hatch that allows it to
be swept.
Be aware of the fact that it is particularly important that
connections have a certain flexibility in order to prevent
movement in the installation leading to cracks.
N.B. A correct and sealed connection is very important for the
proper functioning of the product.
The chimney draught should never exceed 2.5 mm H
when the fireplace is in use. If the draught is too strong you can
install and operate a flue damper to control the draught.
16
In case of chimney fire
•
Close all hatches and vents.
•
Keep the firebox door closed.
•
Check the loft and cellar for smoke.
•
Call the fire service.
•
Before use after a fire an expert must check the fireplace in
order to ensure that it is fully functional.
4.6 Control of functions (fig. 6)
When the product is set up, always check the control functions.
These shall move easily and function satisfactorily.
Jøtul F 602 is equipped with the following controls:
Air vent, fig. 6D
Left position:
Right position:
O (25 Pa)
2
closed
open