EN
Commissioning
1
Mounting
Mounting via holes for M4-sized screws in the case or via a BT 56 / BT 59 mounting
system (accessory).
A Optical axis
B Optical swivel range:
NOTE
Degree of protection IP 65 is achieved only if the connectors and caps
are screwed into place!
2
Electrical connection – Commissioning with factory settings
Connection of the BCL 3xxi via the MS 3xx, MK 3xx, ME 3xx, or via the MA 100
with KB 301 - 3000.
Connect voltage supply and, if necessary, switching input, USB service interface
and host/bus interface.
Switch on operating voltage, PWR LED must illuminate green.
Activate scanner via switching input; the laser switches on.
Hold the following "LEUZE" sample bar code up to the BCL 3xxi at a distance of
approx. 100 ... 200mm.
Upon successful completion of the read operation, the sensor beam switches off
and the read result is shown in the display.
End the reading gate by removing the switching input signal or with the aid of the
key pad / display.
17
Oscillating mirror version = ± 20°