CP-UM-5629JE
Combustion Safety Controller Burner
Interlock Module
Model RX-L80/90
User's Manual for Installation
Thank you for purchasing an Azbil Corporation product.
This manual contains information for ensuring the correct use
of this product.
This manual should be read by those who design and main-
tain equipment that uses this product.
Be sure to keep this manual nearby for handy reference.
Please read "Terms and Conditions" from the following URL
before ordering and use.
https://www.azbil.com/products/factory/order.html
Function setup of this device should be done with the
SLP-RXE/RXM Smart Loader Package before use. This device
will not operate without function settings. For settings-
related instructions, please refer to the manual for Model
SLP-RXE/RXM Smart Loader Package (No. CP- UM-5634JE).
NOTICE
Be sure that the user receives this manual before the product is used.
Copying or duplicating this user's manual in part or in whole is
forbidden. The information and specifications in this manual are
subject to change without notice.
Considerable effort has been made to ensure that this manual is
free from inaccuracies and omissions. If you should find an error or
omission, please contact the azbil Group.
In no event is Azbil Corporation liable to anyone for any indirect,
special or consequential damages as a result of using this product.

SAFETY PRECAUTIONS

Safety precautions are for ensuring safe and correct use of
this product, and for preventing injury to the operator and
other people or damage to property. You must observe these
safety precautions. Also, be sure to read and understand the
contents of this user's manual.
z
Key to symbols
WARNING
Warnings are indicated when mishandling this prod-
uct might result in death or serious injury to the user.
CAUTION
Cautions are indicated when mishandling this product
might result in minor injury to the user, or only physi-
cal damage to this product.
WARNING
Use the unit within the operating ranges recommended
in the specifications (for temperature, humidity, vibra-
tion, shock, installation direction, atmosphere, and so on).
Failure to do so might cause fire or device failure.
If the Smart Loader Package
(SLP-RXE/RXM) is connected
to the RX-L, use the latest
version. Old versions cannot
be connected.
Before installing, removing, or wiring the unit, turn OFF the
power to the unit and any connected devices. Failure to do
so might cause electric shock.
Do not allow wire clippings, metal shavings, water, etc., to
enter the case of this device. Doing so can cause fire or de-
vice failure.
Do not touch electrically charged parts such as the power
terminals. Doing so might result in electric shock.
Before wiring the unit, always turn the power OFF. Not
doing so can cause device failure.
Wire the unit in compliance with established standards,
using the specified power source and recognized installa-
tion methods. Failure to do so might cause electric shock,
fire, or device failure.
The total power consumption of all linked modules should
be 80 W or less. Otherwise there is a danger of fire or device
failure.
Do not supply power to the linked modules from multiple
power sources. Also, do not short the power terminals of
connected modules that are sharing a power source. Doing
so might cause fire or device failure.
Do not use unused terminals on the device as relay termi-
nals. Doing so might cause electric shock, fire, or device
failure.
Do not short the outputs. Doing so can cause device failure.
Firmly tighten the terminal screws. Insufficient tightening
of terminal screws can cause fire.
If there is a risk of a power surge caused by lightning, use a
surge absorber (surge protector) to prevent fire or device
failure.
Operating this module improperly could result in electric
shock, device failure, or fire. Be sure to display warnings to
prevent such accidents at the module installation site.
Since this module has no power switch, be sure to install a
switch for shutoff of the main power to this module in the
control cabinet.
Check that the unit has been correctly wired before turning
the power ON. Incorrect wiring of the module can damage
it or lead to hazardous conditions.
This device contains high voltage components. Do not at-
tempt to disassemble, modify, or repair it. Doing so could
result in electric shock, device failure, or fire.
Always connect interlock contacts and limit device contacts
directly to the interlock input on this unit.
If the system is locked out, do not reset it until the cause of
the problem has been eliminated.
Install this unit in a lockable environment or in a panel that
can be opened and closed only with a tool or key. Touching
a terminal or other part by mistake can result in electric
shock.
This unit has an IP20 protection rating. Install and use it in a
panel that has an IP54 or equivalent rating.
Install or remove the DIN rail locking tab using a tool such
as a screwdriver.
Do not disassemble the unit. Doing so might cause device
failure.
Do not block ventilation holes. Doing so can cause fire or
device failure.
E1
WARNING
CAUTION