Cooling (P2):
The cooling function is generally used for cooling down the primary
solar tank at high solar irradiation. With this function you could
cumulate excess energy on another heat storage. (Swimming pool,
tank ...)
Switch on:
- When the water temperature (T3) inside the tank increase upper
the setting level, adjustable on the parameter menu (N°3 =>default
value 50°C)
Switch off:
- When the water temperature (T3) is 5°C below the setting level.
Example:
T3 setting
T3 setting – 5°C
Parameter N°P1:
P1.A
Automatic mode: The pump P1 will run in accordance
with the "dt" value. (default value)
P1.1
Manual mode: The pump will run during 4 hours and
return automatically in Automatic mode after this time.
P1.O
Manual mode: The pump is switch off.
Use this function to stop the solar loading.
Parameter N°P2:
P2.1
Manual mode: The additional heat is switch on.
P2.0
Manual mode: The additional heat is switch off.
Water temperature in tank T3 (°C)
P3
Main pump control
Extra output control