Parameter N°3: Setting level for extra function
3.50
Setting level to start the extra function (P2).
(Default value 50°C, adjustable xx)
Available only if (T3) sensor is connected.
Parameter N°4: Anti freeze function
This option will keep the solar panel temperature T1 above the
Freeze setting level (see below) by activating the pump P1.
This option could be used to reduce snow accumulation on the
panel and increases the efficiency during the day or to avoid solar
liquid damages.
Careful: it is preferable not to use this function in the too cold
regions in order not to use too much the energy stored in the tank
4.OF
The antifreeze function is deactivated (default value)
4.1
Press the (+) or (-) key to choose the level to start the
anti freeze function.
(Adjustable -20°C to + 7°C)
Parameter N°5: Overheat protections
Panel overheat protection
This option is used to protect the collector liquid and to avoid vapour
in the solar circuit.
It consists to activate the pump if temperature on the collector T1
exceeds the value of parameter N°6 (default value 140°C), even if
the max temperature is reach.
(In all the case the pump will be stopped when the water
temperature in the tank will reach the maximum admissible
temperature 95°C).
System overheat protection
If the temperature was been increased up to 95°C and the collector
temperature T1 is 5°C below. The pump will be activated to cool the
tank until the adjusted value (parameter N°2).
You can deactivate this function on the parameters menu (N°5 =
default value off)

IMPORTANT:

To be sure that all elements of the installation are compatible before
desabeled this function.