Table 1
Primary side circuit flow rate map
Pump output opening/water flow rate
adjust valve opening
Flow rate (pump output opening 16%)
Flow rate (pump output opening 27%)
Flow rate (pump output opening 100%)
(Check result)
Pump output opening/water flow rate
adjust valve opening
Flow rate (pump output opening 16%)
Flow rate (pump output opening 27%)
Flow rate (pump output opening 100%)
4-1 Check the following. (Primary side circuit)
Primary side circuit
↓ Check the checkbox.
□ All places with flow rate valve opening 1000 through 100 are 2 L or above?
If 2 L/min or below, air may not be bled out. Perform an air bleeding operation and water flow rate
adjustment operation again.
□ When there are multiple units, the values of the same pump output opening and the same valve opening
are not greater or less than those for other units by 10% and 2 L/min or more.
(In multiple-unit system, perform a water flow rate adjustment operation at the same time.)
□ All the values (item codes d01 through d09) are not "0" when the pump output opening is 16%. (Not
whole air is bled out.)
Table 2
Secondary side circuit flow rate map
Pump output value
0
Flow rate
d55
Pump output value
55
Flow rate
d66
(Check result)
Pump output value
0
Flow rate
Pump output value
55
Flow rate
4-2 Check the following. (Secondary side circuit)
↓ Check the checkbox.
□ Is the output at 100% (d75) between 20 ℓ/min and 30 ℓ/min?
If the output is below 20 ℓ/min, water may not flow at a high flow rate during normal operation.
If the output is above 30 ℓ/min, water may not flow at a low flow rate during normal operation.
• Take a measure such as adjusting the frequency using an inverter, etc. so that the output at 100% (d75)
becomes between 20 ℓ/min and 30 ℓ/min.
□ Does a value from 1 ℓ/min to 4 ℓ/min exist for the flow rate at an arbitrary output except 0%?
If there was no value from 1 ℓ/min to 4 ℓ/min for the flow rate when any output except 0%, the flow rate
may not be able to be controlled at a low flow rate.
• Carry out the air bleeding and flow rate adjustment operations again.
• Take a measure such as adjusting the frequency using an inverter, etc. so that a value from 1 ℓ/min to 4 ℓ/min
exists for the flow rate during output.
Close
<------------------
1600
1400
d01
d02
d10
d11
d19
d20
Close
<------------------
1600
1400
5
10
15
d56
d57
d58
60
65
70
d67
d68
d69
5
10
15
60
65
70
GB-41
Water flow rate adjust valve opening
1200
1000
800
d03
d04
d05
d12
d13
d14
d21
d22
d23
Water flow rate adjust valve opening
1200
1000
800
20
25
30
d59
d60
d61
75
80
85
d70
d71
d72
20
25
30
75
80
85
Open
------------------>
600
400
200
d06
d07
d08
d15
d16
d17
d24
d25
d26
Open
------------------>
600
400
200
35
40
45
d62
d63
d64
90
95
100
d73
d74
d75
35
40
45
90
95
100
100
d09
d18
d27
100
50
d65
50