Mitsubishi Electric QAHV-N136TAU-HPB Manual De Instrucciones/Instalación página 79

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Running information No.
Running information
No.
001
High pressure operation data [× 0.1 MPa]
002
Low pressure operation data [× 0.1 MPa]
003
Outlet hot water temperature operation data [× 0.1ºF]
004
Outdoor air temperature during operation [× 0.1ºF]
005
Total compressor operation time [× 10 h]
006
Outlet hot water temperature [× 0.1ºF]
007
Inlet water temperature [× 0.1ºF]
008
High pressure [× 0.1 MPa]
009
Low pressure [× 0.1 MPa]
010
Discharge refrigerant temperature [× 0.1ºF]
011
Suction refrigerant temperature [× 0.1ºF]
012
Operating frequency [× 0.1 Hz]
013
Flow sensor [× 0.1 L/min]
016
Secondary side outlet water temperature [× 0.1ºF]
017
Secondary side flow sensor [× 0.1 L/min]
018
Secondary side pump output [%]
Example) No. 001
Remote control display: 38
Actual value: 3.8 MPa
Description
GB-79
Remarks
Data of last hot water storage operation
Current values

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Qahv-n136tau-hpb-bs

Tabla de contenido