3. PROGRAMMING THE DEVICE
1.
Set the number of devices connected to the gateway:
values available: from 1 to 20 devices.
Menu path: Service  Service Settings  Device settings
2.
Set the address and type of device :
Models available: heaterSteam, humiSteam X-plus, humiSteam basic,
gaSteam, generic device
Menu path: Service  Service Settings  Device settings
The address setting and type of model must be selected for each
device connected to the gateway
3.
Set the BMS1 and BMS2 serial port for reading by external
supervisor:
Address, protocol and baud rate setting.
Menu path: Service  BMS Settings
4.
Set the Carel master protocol for communication between
Supernode and devices:
Supernode communication protocol setting with devices: baud rate
(Retry n. and ORT can be left as default)
Note: the baud rate to be set always corresponds to the slowest
device connected (for heaterSteam the baud rate is 9600).
Menu path: Manufacturer  Factory Settings
+050003325 Supernode for humidifi cation - 1.0 - 20.06.2014