1. INTRODUCTION
The gateway can connect up to a maximum of 20 devices (humiSteam Y-X-W, heaterSteam, gaSteam), allowing up to 150
variables (50 analogue, 50 integer, 50 digital) for each connected device to be managed by the external supervisor.
Seven pre-set templates allow the variables exchanged between the humidifi er and the gateway to be addressed
automatically, depending on the device selected during programming: simply specify the type of device and the number
of devices connected. The built-in pGD on the Supernode or an external pGD1 terminal can be used for programming.
Supernode part number:
Description
Supernode for humidifi cation + FLSTDmUGWS
On the external supervisor side, the protocol can be selected by choosing the corresponding optional serial card. The
possible options are:
item
1
Modbus®/CAREL RS485
2
LON
3
BACnet™ Ethernet™
4
BACnet™ RS485
5
KONNEX
The module is DIN rail mounted, with 24 Vac power supply (+10%, -15%).
Supernode for humidifi cation allows the possibility to select UR, UEX, UEW, UEY and UG humidifi ers, including a combination
of diff erent models.
For the address settings of the variables on the supervisor side, refer to the dynamic table, requesting from Carel the
"FLSTDmUGWS_Supervisory_List_dinamic_table_supernode_for_humidifi cation" Excel fi le.
The application on Supernode also features the following options:
•
Edit the humidifi er model, if necessary add/re-address the pre-set variables
•
Manage a generic device using the "Universal" model, which can be freely edited according to customer requirements
P/N
PCOS0004850
PCO10000F0
PCO1000WB0
PCO1000BA0
PCOS00KXB0
3
description
Opto-isolated RS485 serial
LON FTT10 serial
Ethernet™ 8 MB serial
BACnet™ MS/TP 485 serial
KONNEX BMS port serial
+050003325 Supernode for humidifi cation - 1.0 - 20.06.2014
ENG
Carel P/N
SNU0000EM0
tab. 1a