Technical Parameters - Elko EP iNELS Air QS-100 Manual De Instrucciones

Ocultar thumbs Ver también para iNELS Air QS-100:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 13

Technical parameters

Power supply
External power supply:
Input
Measurement of CO
concentration:
2
Sensitivity:
Accuracy:
Temperature measuring:
Sensitivity:
Accuracy:
Humidity measuring:
Sensitivity:
Accuracy:
Light intensity measurement:
Range:
Setting
Alarm Detection:
Indication
Red / green LED:
Detection area:
Recommended installation height:
Communication
Protocol:
RCZ1 868 MHz
Transmitter frequency:
Range in open space:
Approx. 50 km** Approx. 10 km** Approx. 30 km**
Other parameters
Working temperature:
Storage temperature:
Operation position:
Mounting:
Protection degree:
Color:
Dimension:
Weight:
* Multiple frequency bands of B1 / B3 / B5 / B8 / B20 / B28
** Depending on network coverage
AirQS-100S AirQS-100L AirQS-100NB
110 - 240 V AC
YES
300 - 5 000 ppm
5% (0 - 180 ppm)
built-in sensor
-25 .. 70 °C
± 3 °C
built-in sensor
0 .. 90 % RH
± 4 %
built-in sensor
0.045 - 188 000 Lx
message to the server
See manual
max. 40 m
3
max. 4 m
Sigfox
LoRa
NB-IoT
868 MHz
LTE Cat NB1*
0...+40 °C
-30...+70 °C
Horizontal (ceiling) / Vertical (Wall)
screws
IP20
white
Ø 120 x 36 mm
185 g
Warning
Read the operating instructions before installing the device and putting it into opera-
tion. Instruction manual is designated for mounting and also for user of the device. It is
always a part of its packing. Installation and connection can be carried out only by a per-
son with adequate professional qualifi cation upon understanding this instruction man-
ual and functions of the device, and while observing all valid regulations. Trouble-free
function of the device also depends on transportation, storing and handling. In case you
notice any sign of damage, deformation, malfunction or missing part, do not install this
device and return it to its seller. It is necessary to treat this product and its parts as elec-
tronic waste after its lifetime is terminated. Before starting installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and servicing ob-
serve safety regulations, norms, directives and professional, and export regulations for
working with electrical devices. Do not touch parts of the device that are energized – life
threat. To ensure the transmission of the radio signal, make sure that the devices in the
building where the installation is installed are correctly located. Unless otherwise stated,
the devices are not intended for installation in outdoor and damp areas, they must not
be installed in metal switchboards or in plastic cabinets with metal doors - this prevents
transmission of the radio frequency signal. iNELS Air is not recommended for control-
ling life-saving instruments or for controlling hazardous devices such as pumps, heaters
without thermostat, lifts, hoists, etc. - radio frequency transmission may be overshad-
owed by obstruction, interference, transmitter battery may be discharged etc., thereby
disabling the remote control.
3 / 3

Publicidad

Tabla de contenido
loading

Tabla de contenido