2.4
Specification
General data
Dimensions
Height when tilted
Minimum room height for anode replacement
Connections
Connection size, DHW
Connection size, cold water
Connection size, DHW circulation
Internal diameter, test port, solar cylinder temperature sensor
Internal diameter, test port, cylinder temperature sensor
Weight (dry, excl. packaging)
Total weight when filled
Cylinder capacity
Available capacity (total)
Available capacity (excl. solar heating)
1)
Available amount of DHW
2)
DHW outlet temperature
:
45 °C
40 °C
Standby heat loss to DIN 4753 part 8
Maximum throughput, cold water inlet
Maximum DHW temperature
Max. operating pressure, DHW
Highest design pressure (cold water)
Maximum DHW test pressure
Upper indirect coil
Contents
Surface area
Performance factor N
to DIN 4708
L
Continuous output (at 80 °C flow temperature, 45 °C DHW outlet temperature and
10 °C cold water temperature)
Heat-up time at rated output
5)
Maximum heat input
Maximum heating water temperature
Max. heating water operating pressure
Connection size, heating water
Pressure loss diagram
Lower indirect coil
Contents
Surface area
Maximum heating water temperature
Max. heating water operating pressure
Connection size, solar
Pressure loss diagram
Table 4 Dimensions and specification ( Fig. 1, page 63 and Fig. 4, page 65)
1) Without solar heating or reheating; selected cylinder temperature 60 °C
2) Mixed water at the draw-off point (at 10 °C cold water temperature)
3) Distribution losses outside the buffer cylinder are not taken into account.
4) The performance factor N L=1 to DIN 4708 for 3.5 occupants, standard bath tub and kitchen sink. Temperatures: cylinder 60 °C, outlet 45 °C and cold water 10 °C. Measured
at max. heat input. The N
drops with reduced heat input.
L
5) Limit to the stated value for heat sources with higher heat input.
SM290.5 E | SM300.5 | SM400.5 E – 6 720 819 314 (2016/04)
3)
4)
Unit
SM290.5 E
Fig. 1, page 63
mm
1945
mm
2000
Table 6, page 40
DN
R1"
DN
R1"
DN
R¾ "
mm
19
mm
19
kg
115
kg
405
l
290
l
120
l
171
l
200
kWh/24h
2.1
l/min
29
°C
95
bar (positive)
10
bar (positive)
7.8
bar (positive)
10
l
5.7
2
m
0.84
NL
1.8
kW
23
l/min
9.4
min
16
kW
31.5
°C
160
bar (positive)
16
DN
R1"
Fig. 2, page 64
l
5.8
2
m
1.3
°C
160
bar (positive)
16
DN
R1"
Fig. 3, page 64
Product information
2
SM300.5
SM400.5 E
1655
1965
1850
2100
R1"
R1"
R1"
R1"
R¾ "
R¾ "
19
19
19
19
118
135
408
515
290
380
125
155
179
221
208
258
2
2.2
29
38
95
95
10
10
7.8
7.8
10
10
6.2
7.0
0.9
1
2
3
28.5
36
11.7
14.7
18
18
28.5
36
160
160
16
16
R1"
R1"
8.8
12.1
1.3
1.8
160
160
16
16
R1"
R1"
39