Set up web server on the remote access portal
· No router settings are required to operate via the portal.
1.
Enter the portal web address from the package insert in the web
browser on the PC/laptop.
2.
Select language.
3.
Create new account ("Sign up") using a personal e-mail address
and activation code (provided on the package insert).
4.
Log in using the password received by mail.
After initial log in, the user is requested to change the password.
5.
Fill out plant information and activate the device.
6.
Click the plant link.
7.
Using an existing account, the device is activated after log in
under "Administration".
8.
Navigation: Primary navigation (horizontal menu), secondary
navigation (vertical menu) and path navigation (levels below the
primary menu).
9.
Return navigation: Click the symbol
via path or primary navigation.

Change local administrator password

· The local administrator password for the web server must be
changed to prevent unauthorized access to the web server.
10. Under primary navigation, select "User accounts".
11. Click the red pencil .
12. Create new password.
13. Click [OK].

Create device list

· The Web server monitors only the bus devices listed in the device
list.
14. Select "Device web pages" from primary navigation. The device
list opens and the Web server appears in the device list.
15. Add new bus device: Click [Add].
16. Enter LPB address (for LPB only). The first bus device is
addressed with 0.1 (segment 0, device 1) as the default.
Finish with [OK].
· The Web server searches for the corresponding bus device.
It appears in the device list.
17. Add other bus devices: Repeat steps 15 and 16.
18. Check the box for all devices in the device list
19. Click [Generate] and wait until the message "Process finished"
appears. This may take a few minutes.
Result: In the device list, the Web server and the bus devices display
the status "Generated".
en 8 / 8
2014-10-01
"Upward" or navigate
.
G5711xx
74 319 0703 0 d

Web server settings

· Edit settings: Click the red pencil symbol .
20. Select "Home" from primary navigation:
Home > 0.5 OZW672...
21. ...> Time of day/date: Time of day/date
22. ...> Settings > Web server: Language
23. ...> Settings > Time of day/date:
Summer time start, Winter time start
24. ...> Settings > Communication > :
Device number, Clock time source
· Additional information on e-mail transmission of faults, system
report, "Energy Indicator" and trend is available in the
commissioning guide C5711.

Final check on web server

· Message inhibition and addressing mode must be switched off.
25. Remove the cover.
26. Switch (8) must be set to OFF
· ON LED (1)
must be green or orange.
· Fault LED (4)
should be unlit.
27. Remount the cover.
.
Siemens Building Technologies