Mounting
1
3b
See Figures
through
1
1.
Take off cover
2.
Insert cable tie for cable
3a
Standard mounting on standard rail TH 35-7.5
1.
Mount standard rails.
2.
Attach Web server to standard rails.
3.
Press until Web server clicks in place.
3b
Screw on mounting on a level wall
Drill two holes for the screws Æ max. 3.5 mm.
1.
2.
Tighten Web server.
- Make sure the unit is flat (i.e. housing is not warped)
- See "Dimensions" for sizes.
Notes
· Must be mounted vertically for > 35 °C ambient temperature
(circulation through ventilation slots).
Wiring
4
8
See Figures
through
1.
Turn off bus device!
2.
Attach LPB/BSB cable to A
4
terminal 3 (MB/CL-)
3.
Connect potential-free contacts to D1, M, or D2, M as required
4
4.
Tighten cable tie and cut off the remainder
5.
Break out the notch from the cover
7
6.
Replace the cover
7.
Connect Web server to power
The Web server is operational, when the ON LED is green or
orange.

Display and operating elements

9
See Figure
LED displays
1 ON
(red/green/orange)
Dark
No power.
Steady red
Web server starting (operating system).
Flashing red
Web server starting (application).
Steady green/orange
Web server operational, "Energy indicator = Green
leaf or Orange leaf".
Flashing green/orange
Web server is connected to the remote access portal
2 LPB/BSB A
(green)
Dark
No bus power.
Lit
LPB/BSB operational.
Flashing
Communication on LPB/BSB.
3 (LED) B
Dark
No function.
4 Fault
(red)
Displays faults from the Web server or the connected bus device:
Dark
No fault.
Lit
Acknowledged fault.
Flashing
Unacknowledged fault
5 (LED)
Dark
No function.
Siemens Building Technologies
2
, terminal 2 (DB/CL+) and
5
6
8

‚.
+
Operating buttons
The following applies when pressing the buttons:
Short:
<2 seconds.
Long:
<6 seconds.
6 Remote
Short
No function.
Long
Sends system report to the configured fault e-mail
receivers; see as well "Button combination".
7 Service button
Short
No function.
Long
See "Button combination".
Button combination
and
Short
No function.
Long
Reestablishes default state.
Note on "default state":
· All configuration data and settings are reset.
· The device list, plant diagrams, and unsent messages are deleted.
· History data is not deleted.
Commissioning
8
See Figures
through
Caution
· Web server connects automatically to the remote access portal as
soon as it has internet access via the Ethernet interface.
· Commissioning guide C5711 has information on the remote access
portal (www.siemens.com/ozw672-manual).
· Disabling the automatic connection to the portal and commissioning
without the portal is described in commissioning guide C5711.
Prerequisites
· Web server is mounted, wired, and connected to the Internet via the
Ethernet interface.
· The connected bus device is commissioned.
· The bus device has a valid LPB/BSB address and is operational.
· Bus power supply to the LPB/BSB bus is turned on.
· Recommendation: The bus device is clock slave and set remotely.
· Operating voltage for the web server is switched on.
The web server is ready as soon as the On LED is green or orange.
· PC/Laptop has the same or other Internet access.
74 319 0703 0 d
G5711xx
9
2014-10-01
en 7 / 8