SG4 FIELDBUS
6.8 ESTRUCTURA DE DATOS DE PROCESO
6.8.1
Byte de control
El byte de control representa una serie de datos transmitidos por el PLC a la barrera de luz.
La tabla a continuación muestra en detalle el significado de cada bit.
Bit
Nombre
0
Reset
1
MutingActivated
2
BlankingActivated
3 -7
Reserved
Los puntos de datos del byte de control son accesibles en SafeDESIGNER como canales de salida seguros.
Función
Acknowledge
The control bit "Reset" is used to acknowledge an error state or
(depending on the configuration) to acknowledge startup.
Acknowledgement is done by a transition from logical FALSE
(zero) to logical TRUE (one).
Signals if muting is active on the ESPE device
0: Muting is not active on ESPE device (default value if muting is
not supported by device)
1: Muting is active on ESPE device
Signals if blanking is active on the ESPE device
0: Blanking is not active on ESPE device (default value if feature
is not supported by device)
1: Blanking active on ESPE device
Fig 38 - Canales de salida seguros
42/76