To Charge Additional Refrigerant; To Fix The Fluorinated Greenhouse Gases Label; Connecting The Electrical Wiring; About Electrical Compliance - Daikin altherma 3 R Instrucciones De Instalación

Ocultar thumbs Ver también para altherma 3 R:
Tabla de contenido

Publicidad

4 Installation
4.5.2

To charge additional refrigerant

WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
4.5.3
To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
1
=
f
GWP: XXX
2
=
2
1
1
+
2
=
GWP × kg
=
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
f
GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label. That GWP is based on the current legislation on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
Installation manual
10
a
kg
b
kg
c
kg
d
e
tCO
eq
2
equivalent.
2
equivalent.
equivalent
2
4.6

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
4.6.1

About electrical compliance

Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
4.6.2
Specifications of standard wiring
components
Component
(a)
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire sizes
Interconnection cable
Recommended field fuse
Earth leakage circuit breaker
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
4.6.3
To connect the electrical wiring to the
outdoor unit
1 Remove the switch box cover.
2 Connect the interconnection cable and power supply as follows.
Ensure stress relief by using the wire clamp.
EN/IEC  61000‑3‑12
(European/
ERGA04DAV37
19.9 A
230 V
1~
50 Hz
Must comply with applicable
legislation
Minimum cable section of
1.5 mm² and applicable for
230 V
20 A
Must comply with applicable
legislation
ERGA04DAV37
Daikin Altherma 3 R
4P618926-1 – 2020.03