420010294601 BLU 7000.1 - 12000.1 PR
EN
+
Part. 2
SELECTOR
COMMUTATORE
0
0 =
=
=
AUTO =
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas flow,
as established by analyzing the combustion process.
Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the gover-
nor.
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on
the counter and the time of the reading in seconds.
Proceed with the calculation using the following :
+
AUTO
operating elements locked in an inter-
bloccaggio degli apparati per il
mediate position
funzionamento in una posizione intermadia
operation on maximum capacity
funzionamento alla massima potenza
funzionamento alla minima potenza
operation on minimum capacity
funzionamento automatico
automatic operation
ADJUSTING THE MAXIMUM CAPACITY OF THE GAS
ADJUSTING THE MAXIMUM AIR FLOW RATE
ADJUSTING THE INTERMEDIATE BURNER CAPACITY
AIR ADJUSTMENT
e x f = kW
sec
14
- -
+
Part. 3
e
= Litres gas
sec = Time in second
G20 = 34,02
f
G30 = 116
G31 = 88