Paragraph 3 – Dosage Proportional to the Potential Redox Measurement (O.R.P.)
Programming
PROG
Configuration
Pump Funtions
-
+
Pump
Functions
Redox Measure
Setpoint
-
560 mV
Setpoint Type
-
High
Prop. Band
-
50 mV
Alarm Band
-
200 mV
O.F.Alarm
-
0m
Probe Calib.
-
On
Display during Operation
Setpoint type;
High/Low
Alarms and statuses
Cal = calibration not
completed
Lev = Level alarm
Flw = Flow alarm
Alm = Measurement
outside alarm band
OFA = O.F.A. alarm
Paragraph 4 – Setting the Maximum Flow
Programming
PROG
-
Pump Functions
Max flow rate
Max flow rate
P100%
P100%
-
Max flow rate
F320s/m
EM00136063
The pump measures and controls the pH of a solution, programming in
sequence: set-point, set-point type, proportional band and alarm band
Set-point type: maximum
s/m
max
flow-rate
Set-point type: minimum
-
s/m
+
-
max
+
flow-rate
-
+
-
+
-
It is also possible to programme:
+
- the O.F.A. (Over Feed Alarm) time in minutes, or rather a time beyond
-
which an alarm signal is triggered if the pH value does not reach the set-
+
point.
- The measurement resolution (1 or 2 decimal points)
- Deactivation/activation of the calibration procedure
The maximum frequency can be modified during operation, by pressing
the
keys to decrease it.
Flow sensor status
Potential Redox.
measurement value
F
F F
High
560mV
Lev
Stop
P100%
Current dosage value
(depends on the selected unit
of measurement)
Pump status
Empty = pump in start
Stop = pump stationary
Paus = pump in pause
-
+
-
-
+
-
Pump Off
0
Alarm Band
Proportional
Band
0
Alarm Band
keys at the same time to increase the flow, or the
Percentage, Frequency,
l/h, Gph, ml/m
This makes it possible to set the maximum flow offered by
the pump, and the programmed mode (% or frequency) is
used as the standard unit of measurement when displaying
the flow. Changes can be made by pressing the
then using the
to confirm and return to the main menu
rev. 2.2 EN
Operation
Proportional
Band
Alarm Band
Pump Off
Alarm Band
Display during Setting (MODE key)
Displays in sequence
SP = Setpoint value
BP = Proportional band value
BA = Alarm band value
OFA = O.F.A. value
SP
560mV
450mV
P100%
Maximum set dosage value
(depends on the selected unit of measurement)
Percentage, Frequency, l/h, Gph, ml/m
Operation
keys to set the new value. Press
mV
mV
Measurement value
della misura.
key,
5