Installation Requirements - E2S BEDS120D Serie Manual De Instrucciones

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 23
2) Marking
All units have a rating label, which carries the following
important information:-
BExDS120D or BExDS110D
Unit Type No.
Input Voltage: DC Units
AC Units
Codes:
Ex d IIC T4 for Ta –50ºC to +55ºC
Ex d IIB T4 for Ta –50ºC to +70ºC
Ex tD A21 IP67 T115ºC based on max Ta of +70ºC
KEMA 99ATEX6312
Certificate No's
IECEx KEM 10.0003
Epsilon x:
Equipment Group and
Category:
CE Marking:
Notified Body No.
"Warnings
"
DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC

4) Installation Requirements

Sounders must be installed in accordance with the following
or equivalent standards.
EN60079-14:2008
IEC60079-14:2007 (Ed4)
EN60079-10:2003
IEC60079-10:2008 (Ed1)
Installation should only be carried by competent personnel
and any local codes of practice applied.
5) Zones, Gas Group, Category and Temperature
Classification
The units can be installed in locations with the following
conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. BExDS120D and BExDS110D (Gas-Dust) English
INSTRUCTION MANUAL (ATEX / IECEx)
BExDS120D and BExDS110D
For use in Flammable Gas and Dust Atmospheres
12V or 24V or 48V
230V or 110V or 115V
II 2G/D
0518
Electrical Installations in Hazardous
Areas (other than mines)
Classification of Hazardous Areas
Gas Groupings:
Group IIA
Group IIB
Group IIC < +55ºC
Temperature Classification:
Area Classification Dust:
Zone 21
Explosive dust air mixture likely to occur in
normal operation.
Zone 22
Explosive dust air mixture not likely to occur,
and if it does, it will only exist for a short time.
IP Rating:
Equipment Category:
Ambient Temperature Range:
-50°C to +55°C Gas Groups IIA, IIB and IIC
-50°C to +70°C Gas Group IIA and IIB
6) Sounder Location and Mounting
See drawing A
7) Access to the Flameproof Enclosure
See drawing B
Note the four M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on these
sounders. It is therefore important that these screws and
their spring washers are kept in a safe place during
installation.
8) Power Supply Selection
The system power supply must have the necessary capacity
to provide the input current to all of the sounders connected
to the system.
The following table shows the input current taken by the
various sounder units:-
Unit Type
BExDS120D
BExDS120D
BExDS120D
BExDS120D
sales@e-2-s.com
Issue E
(Four Sheets)
19-02-10
Flameproof Sounders
Propane
Ethylene
Hydrogen and Acetylene
o
T1
400
C
o
T2
300
C
o
T3
200
C
o
T4
135
C
IP67
T100ºC Ta < +55ºC
T115ºC Ta < +70ºC
2G/D
Input
Input
Voltage
Current
24V DC
800mA
12V DC
850mA
48V DC
420mA
230V AC
90mA
Tel: +44 (0)208 743 8880
www.e-2-s.com
Fax: +44 (0)208 740 4200
(GBR)
Max.
I/P Volts
30V
15V
58V
264V
)