Installation and User Manual
Image 4. Alternative installation location
for the sensor when using the contactor
casing WE 3 and the Digi 1 or 2
control panel. Sensor OLET 19
Image 4 Sensor ceiling installation (OLET 19)
Power
Saunaroom
Volume
min.
max.
kW
m³
m³
4,5
4
6
6,0
5
9
8,0
8
13
Table 1 Safety clearances
Power
kW
4,5
6,0
8,0
Table 2 Cable and Fuse
2.10 Mains connection
The sauna heater must be connected to the mains by a qualified electrician and in compliance with current regula-
tions. Sauna heater is connected with a semi-permanent connection. Use A07BB-F or H07RN-F (60245 IEC 66)
cables or a corresponding type. Other output cables (signal lamp, electric heating toggle) must also adhere to these
recommendations. Do not use PVC insulated cable as a connection cable for the sauna heater.
A multipolar (e.g. 7-pole) cable is allowed, if the voltage is the same. In the absence of a separate control current
fuse, the diameter of all cables must be the same, i.e. in accordance with the front fuse. For example, in an 8 kW
sauna heater the diameter of separate cables to the signal lamp and the mains control unit has to be at least 2.5
mm².
Ring Wall D
OLET 19
Minimum distance to
Height
Side
In front
wall
of
A
D
mm
min. mm
mm
1900
50
50
1900
70
70
1900
100
100
Power supply cable H07RN –F/ 60245 IEC 66
mm²
400V - 415V 3N~
5 x 1,5
5 x 1,5
5 x 2,5
Image 5. NOTE: Only ceiling installation when using the
control panels 1418-2-1517-3 (OT-2-PS-3) and
1418-2-1519 (OT-2-PUi).
The sensor must not be installed on the wall when using the
Ring wall D Heater
Image 5 Sensor ceiling installation (OLET 6-1)
Floor
Ceiling
F
K
B
mm
mm
mm
mm
1200
120
170
230
1250
120
190
230
1250
120
220
230
OLET 6-1
Stone
J
Circa kg
37
37
37
Fuse
A
3 x 10
3 x 10
3 x 16
8