Descargar Imprimir esta página

Scame ROCKER-EX Instalación Uso Y Mantenimiento página 12

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 24
ROCKER-EX[GD]
2.1 TYPE VERSIONS
The ROCKER-EX[GD] in according to the EN 60669-1, are available in the followings type:
Part Number (*)
592.R001-xx-y (**)
Change Over
592.R002-xx-y (**)
592.R003-xx-y (**)
Push Button
Table - 1
(*) The part number can have a suffix, which identify the version (not influence the type of protection).
(**) xx = suffix which identify the threads of the cable entry:
01 = 1 x M20 x 1,5
02 = 2 x M20 x 1,5
03 = 1 x M20 x 1,5 + 2 x M20 x 1,5
04 = 1 x M25 x 1,5 + 2 x M20 x 1,5
05 = 2 x M20 x 1,5 + 2 x M20 x 1,5
06 = 1 x M25 x 1,5
07 = 2 x M25 x 1,5
08 = 1 x M25 x 1,5 + 2 x M25 x 1,5
(**) y = suffix which identify the ambient temperature range:
- = -35°C / +60°C with plastic Ex e cable gland for non-armoured cable
A = -50°C / +60°C with metal Ex e cable gland for non-armoured cable
B = -50°C / +60°C with metal Ex e cable gland for armoured cable
2.2 CERTIFICATES
Atex Certificate
INERIS 19 ATEX 0014X
IECEx Certificate IECEx INE 19.0012X
2.3 CROSS SECTIONAL AREAS CONDUCTORS & TORQUE
ROCKER-EX[GD](In)
Terminals
Earth-Terminal
Table - 2
MP39674
Max.
Max.
Type
Current
Voltage
ON-OFF
switch
250Vca
16AX
Switch
50/60Hz
Terminals Contacts - Torque
Cross Sectional Areas Conductors
Contacts
Wiring Diagrams
2
4
2
4
2
4
2NO
1
3
1
3
1
3
2
1NO
2
2
+
1NC
3
1
1
3
1
3
2
4
2
4
2
4
1NO
+
1
3
1NC
1
3
1
3
2,5 mm²
2,5 mm²
12
Fixed
screws
M4x22mm
In AISI
Tightening Torque - (Nm)
1.2
1.2
ZP91033-1
4 x

Publicidad

loading

Este manual también es adecuado para:

Rocker-gd