1 • INSTALLATION
• Dimensions and cut-out; panel mounting
63
48
48
99
10
Panel mounting:
Fix the device with the bracket provided before making any electrical
connections.
To mount two or more devices side by side, use the cut-out dimensions
shown above.
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC
Directive 89/336/EEC with reference to the generic Standard CEI-
EN61000-6-2 (immunity in industrial environments) and EN50081-1
(emission in residential environments). BT (low voltage) conformity to
Directive 73/23/EEC as modified by Directive 93/68.
MAINTENANCE: Repairs must be done out only by trained and
specialized personnel. Cut power to the device before accessing
internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene, etc.). Use of these solvents can reduce the
mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes
defects caused by any use not conforming to these instruction.
EMC conformity has been tested with the following connections
FUNCTION
TC input probe
"PT100" input probe
Power supply cable
Relay output wires
Serial connection wire
40T 48
TEMPERATURE INDICATOR - ALARM UNIT WITH CONFIGURABLE INPUT
70
45
45
!
For correct and safe
installation, observe the
warnings contained in
this manual.
CABLE TYPE
LENGTH
USED
0,8 mm
2
compensated
5 mt
1 mm
2
3 mt
1 mm
2
1 mt
1 mm
2
3,5 mt
0,35 mm
2
3,5 mt
INSTALLATION and
OPERATION MANUAL
SOFTWARE VERSION 3.2x
code 81642C / Edition 10 - 12/04
2 • TECHNICAL SPECIFICATIONS
Accuracy
Resolution
(function of settable sample
Main input
70
TC Type
Thermocouples (ITS90)
Cold junction error
RTD Type (scale configurable
within indicated range, with or
without decimal point, ITS90)
Max. RTD line resistance
PTC Type/ NTC Type
Max. non-linearity error
°C / °F selection
Linear scale ranges
Logic input
Function of logic input
(Trip points)
masking
Relay contacyt
Logic output
Triac output
Fault settings
(option) Transmitter / Sensor
Power Supply
(option) Analog
retransmission
Power supply
(switching)
Faceplate protection
Working / Storage
temperatures
Relative humidity
Environmental conditions of use
Installation
10
(includes R77 version)
4 digit red digit height 10mm
Display
3 mechanical keys (Raise, Lower, F)
Keys
0.2% f.s. at 25°C ambient temperature,
ts =120msec
120msec, >14bit-16000 points
60msec, >14bit-16000 points (only for linear inputs)
30msec, >13bit - 8000 points (only for linear inputs)
time)
15msec, >12bit - 4000 points (only for linear inputs)
TC, RTD, PTC, NTC
60mV, 1V Ri ≥ 1MΩ, 5V, 10V, Ri ≥10KΩ
20mA, Ri = 50Ω. adjustable digital filter
J, K, R, S, T, B, E, N
(IEC 584-1, CEI EN 60584-1, 60584-2)
L GOST, U, G, D, C. Custom linearization
available on request
0,1° / °C
DIN 43760 (PT100), JPT100
20Ω
990Ω, 25°C / 1KΩ, 25°C
See tP parameter
Faceplate configurable
-1999...9999 Configurable decimal point
position, possible 32 segment linearization
24V, 5mA (Ri = 47KΩ) 1500 V isolation or
voltage-free contact
configurable to reset memory latch, hold, flash,
zero, select max./ min. peak, peak-peak value
Maximum of three configurable alarms:
Alarms
absolute, deviation, symmetrical deviation.
Adjustable hysteresis
- exclude on power-up
Alarm
- latch reset from key and/or external contact
- insert delay filter
(DON, DBI, DOF, DPO)
- set minimum intervention time
NO (NC) 5A, 250Vac / 30Vdc
24Vdc, Rout = 500Ω (10V/20mA)
limitation to 30mA
20...240Vac ±10%, 1A max. Snubberless,
inductive and resistive load I
Alarm states can be configured in probe fault
condition
24V ±10%, 50mA
15V for transmitter, max. 50mA
1,2V for potentiometer > 100Ω
10V / 20mA on max. 500Ω resolution 12 bits
(standard) 100...240Vac/dc ±10%, 50/60Hz, 8VA
(optional) 11...27Vac/dc ±10%, 50/60Hz,8VA
IP65
0...50°C / -20...70°C
20...85% Ur non-condensing
for internal use only, altitude up to 2000m
Panel mounting, extractable from front
160 g