Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation

Installation
Step 1: Install mounting bracket to wall
NOTE: Make sure that, when mounted, the unit will
measure 33–45 inches from the top of the sprayheads to
the fi nished fl oor. For use as an eye/face wash, the top
of the sprayheads of the unit must be 33–45 inches from
where the user stands per ANSI Z358.1. The unit must
also be placed a minimum of 6" away from the nearest
wall or obstruction.
1. Install three suitable wall anchors for use with
bolts (supplied by installer) into the wall at the
desired location.
2. Mount the bracket to the wall using three
(supplied by installer).
NOTE: Local codes may require the installation of a
backfl ow prevention valve to complete proper installation.
Compliance with local codes is the responsibility of the
installer. Valve must be tested annually to verify that it
is functioning properly. Backfl ow prevention valves are
not included with the fi xture and may be supplied by the
contractor or purchased from Bradley Corporation.
Step 2: Assemble components
1. Assemble the components as shown on page 4.
• Apply pipe sealant to all pipe joints.
Step 3: Connect water supply
1. Connect the water supply to the unit (piping
supplied by installer).
2. Mount the safety sign to the wall using the sign-
mounting hardware supplied by installer.
3. Open the water supply line. Test for leaks and
adequate water flow.
Bradley Corporation • 215-085 Rev. L; ECM 08-539
(273mm)
3
"
8
3
" bolts
8
4
3
"
8
(111mm)
2"
(51mm)
7
"
8
(22mm)
10¾"
8¾"
(222mm)
2"
(51mm)
2"
(51mm)
4"
(102mm)
Bracket Mounting
6/12/09
S19-630
15"
(381mm)
33"–45"
(838mm–1143mm)
to Finished Floor