I-303
TYPES OF TIMER
-
TYPES DE TEMPORISATEUR - TIPOS DE TEMPORIZADOR
TEMPO TYPES - TYPES TEMPO -
TIPOS TEMPO
1 – ON/OFF Cyclic activated per voltage (Equivalent to I-10 / I-11 / I-12 modules)
When you connect the power supply, the relay is activated during the ON time. Once the ON time finished, the relay will be deactivated during the OFF
time. After the OFF time, the ON time start again.
2 - OFF/ON Cyclic activated per voltage
When you connect the power supply, the OFF time starts without activate the relay. Once the OFF time finished, the relay will be activated during the
ON time. After the ON time, the OFF time start again.
3 - ON/OFF Cyclic activated per push button
When you close the START push button, the relay is activated during the ON time. Once the ON time finished, the relay will be deactivated during the
OFF time. After the OFF time, the ON time start again.
4 - OFF/ON Cyclic activated per push button
When you connect the power supply, the OFF time starts without activate the relay. Once the OFF time finished, the relay will be activated during the
ON time. After the ON time, the OFF time start again.
5 - ON/OFF Cyclic reset activated per push button
When you close the START push button, the relay is activated during the ON time. Once the ON time finished, the relay will be
deactivated during the OFF time. After the OFF time, the ON time start again. If during the ON or OFF timing, you close the START push button, the
timer will be reseted.
6 - ON/OFF Cyclic timed activated per push button
When you close the START push button, the timing is started, and the relay will be cyclically activated and deactivated during the ON time. ON time to
adjust operating timing. OFF Time to adjust the cyclic activation and deactivation timing of the relay.
7 - ON/OFF Cyclic timed activated per voltage
When you connect the power supply, the timing is started, and the relay will be cyclically activated and deactivated during the ON time. ON time to
adjust operating timing. OFF Time to adjust the cyclic activation and deactivation timing of the relay.
8 – Delayed & Timed activated per voltage (Equivalent to I-33 / I-34 modules)
When you connect the power supply, the OFF timing without activates the relay. Once the time finished, the relay is activated during the ON time.
9 – Delayed & Timed activated per push button (Equivalent to I-33 / I-34 modules)
When you connect the START push button, the OFF timing without activates the relay. Once the time finished, the relay is activated during the ON time.
10 - Delayed & Timed reset activated per push button
When you close the START push button, the OFF timing without activates the relay. Once the OFF time finished, the relay will be activated during the
ON time. If during the ON or OFF timing, you close the push button, the timer will be reseted.