Note: Pulsar CT comes with the output
neutral earthed. To change the earthing
system and move to the unearthed neutral
mode, proceed as follows:
c stop Pulsar CT and de-energise it by
unplugging the utility power connection lead
4 (see page 1),
c open Pulsar CT's cover (see fig. 1),
c remove the load receptacle cover (fixed by
a screw, see fig. 2),
N/
c loosen the 2 screws corresponding to the
wire marked N/
,
USE
c remove the wire marked N/
as shown on
the figure 2,
c screw again the 2 screws being careful to
the good position of the remaining neutral
wire,
c put the load receptacle cover back in place,
c close the Pulsar CT's cover.