Behaviour on voltage return
Timer behaviour, voltage re-
turn
Switch-off warning
Priority, lock-out protection
Priority, restraint
Priority, wind alarm
Priority, sun protection
Priority, twilight
Switch-off on brightness
overshoot
82581923
J0082581923
On
Off
Last value
Configured brightness
Basic setting: Off
Off
Restart
Basic setting: Off
On, Off
Basic setting: Off
0...4
Basic setting: 1
0...4
Basic setting: 2
0...4
Basic setting: 3
0...4
Basic setting: 0
0...4
Basic setting: 0
On, Off
Basic setting: On
13/17
Defines the behaviour of the
output after voltage return.
RMD design: Bus voltage re-
turn
Specifies whether the timers
for switch-on delay, switch-off
delay and run-on time remain
off after voltage return or
whether they restart. Directly
connected to the parameters
"Switch-on delay", "Switch-off
delay" and "Run-on time".
If the switch-off warning is ac-
tive, the light is not switched
off directly. The light goes off
30, 15 and 6 seconds before
permanent switch-off. During
the switch-off warning, a
switch-on telegram effects di-
rect switch-on. It is not possi-
ble to terminate the time using
a switch-off telegram.
Specifies the priority for reca-
lling and removing a scene of
type Lock-out protection for
the channel.
Specifies the priority for reca-
lling and removing a scene of
type Restraint for the channel.
Specifies the priority for reca-
lling and removing a scene of
type Wind alarm for the chan-
nel.
Specifies the priority for reca-
lling and removing a scene of
type Sun protection for the
channel.
Specifies the priority for reca-
lling and removing a scene of
type Twilight for the channel.
Allows automatic switch-off
according to the brightness. If
the parameter is On, then the
light controller switches off au-
tomatically when the bright-
ness setpoint is greatly excee-
ded. This parameter is not yet
active, as a light controller has
not yet been implemented.
22.07.2016