Jung FMAS816REG Instrucciones De Servicio página 14

Actuador pulsador/de conmutación 8 fases/actuador persianas 4 fases enet, carrildin
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

eNet
Actuador pulsador/de conmutación 8 fases / actuador persianas 4 fases
eNet, carril DIN
Switch-on on brightness un-
dershoot
Invert switching output
Minimum switching repeat ti-
me
Operating hours
Settings, "Venetian blind" channel
Parameters
Manual commissioning
82581923
J0082581923
On, Off
Basic setting: Off
On, Off
Basic setting: Off
100 ms ... 10 sec
Basic setting: 100 ms
0...65535
Basic setting: Current value
Setting options, Basic set­
ting
On, Off
Basic setting: On
14/17
Allows automatic switch-on
according to the brightness. If
the parameter is On, then the
light controller switches on au-
tomatically when the bright-
ness setpoint is greatly un-
dershot. We recommend only
using the parameter in con-
nection with the parameter
"Switch-off on brightness
overshoot". This parameter is
not yet active, as a light con-
troller has not yet been imple-
mented.
Inverts the switching output
from NO contact function (fac-
tory setting) to NC contact
function
Limits the switching speed of
the device by increasing the
value, in order to protect the
load, for example. Only when
the set time has elapsed is
switching possible again. The
last command during the bloc-
king time is executed after a
delay. The switching repeat ti-
me starts after each switching
operation.
The time is counted during
which the load is physically
switched on (relay contact clo-
sed).
This parameter can be reset to
"0", for example after exchan-
ging the load.
The Reset button is used to
reset the meter to "0". The de-
vice must be programmed to
apply the change.
Explanations
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device can-
not be reset to the factory set-
ting.
22.07.2016