5.2.3 Internal layout of LC 221
Figure 10 shows the internal layout of LC 221.
Fig. 10 Internal layout of LC 221 (three-phase PCB as example)
Pos.
Description
1
Terminals for power supply
2
Terminals for connecting pump 1
3
Terminals for thermal switch, pump 1
4
Terminals for external alarm (outside the tank)
5
Terminals for external reset
6
Terminals for common fault
7
Terminals for high water-level alarm
8
Terminals for failure, pump 1
9
Terminals for operation, pump 1
Terminals for level switches (optional)
10
Terminals for additional high water-level alarm
(inside the tank)
11
Terminals for analogue sensor
12
Service connector to PC Tool
13
Connector for GENIbus interface module
14
Control circuit fuse
15
Piezoresistive pressure sensor module
16
DIP switches (not in use for this application)
17
Connector for battery, 9 V (accessory)
Note: Cable connections for pos. 6-11:
Use a cable tie if leads protrude more than
20 mm from the cable sheath.
Comments
230 V
230 V
Potential-free changeover NO/NC
contacts with max. 250 V / 2 A.
Attention: Connect these terminals
to supply network potential or low
voltage, but do not mix the two.
Digital
Digital
0-5 V or 4-20 mA
Fine-wire fuse:
100 mA / 20 mm x ∅5
0-5 V
Terminal designation
PE, N, L3, L2, L1
PE, N, W1, V1, U1
T1, T2
11, 12
13, 14
X11
X10
X8
X6
81-88
81, 82
91 (GND), 92 (Signal), 93 (12 V)
-
-
-
-
-
-
17