Airzone KNX- Manual De Instalación página 31

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
Object number
Name
Function
Description
Possible values
Type of access to the Bus
Data point identification
10
COMBINED COOLING mode
On/Off
This communication object allows activating/ deactivating the AC unit operation mode
that is connected to system 1, switching to the COMBINED COOLING mode when the
object value is 1 and returning to the mode active in system 1 in case the mode value
is 0.
This mode can only be activated when it is available by the machine/module that is
connected to the system.
0 → Combined Cooling mode Off; 1 → Combined Cooling mode On
Reading/Writing
1.001
11
Minimum set temperature value in cooling mode
Temperature
This value sets the zone minimum temperature by the thermostat in cooling mode.
18º... 26ºC, with a resolution of 1ºC
Reading/Writing
9.001
12
Maximum set temperature value in heating mode
Temperature
This value sets the zone maximum temperature by the thermostat in heating mode.
21º... 30ºC, with a resolution of 1ºC
Reading/Writing
9.001
13
Outdoor sensor temperature
Temperature
This value allows reading the temperature value that has been measured by means of
the outdoor sensor if this element is connected to the system.
0º... 99.9ºC, with a resolution of 0.1ºC
Reading
9.001
31