System cooling demand
Status
The status register value can be read through this object, which indicates whether the
Airzone's zoning system is in cooling demand.
0→ Inactive; 1→ Active
Reading
1.011
19
System heating demand
Status
The status register value can be read through this object, which indicates whether the
Airzone's zoning system is in heating demand.
0→ Inactive; 1→ Active
Reading
1.011
Z. 1
Z. 2 Z. 3
Z. 4
Z. 5 Z. 6
Z. 7
20
30
40
50
60
70
Zone x - Communication error
Status
This communication object allows the gateway to interpret the communication errors
produced in the different zones.
0 → No Alarm; 1 → Alarm
Reading
1.005
Z. 1
Z. 2 Z. 3
Z. 4
Z. 5 Z. 6
Z. 7
21
31
41
51
61
71
Zone x – SLEEP mode
Sleep mode
This communication object allows to access to the configuration register of the zones
and to modify the register value to activate/deactivate the Sleep mode, indicating the
time during which it will remain activated.
0→ Sleep mode Off; 1800→ Sleep mode 30 min.; 3600→ Sleep mode 60 min.; 5400→ Sleep mode 90 min.
Reading/Writing
7.005 (DPT_TimePeriorSec)
Z. 8
Z. 9 Z. 10 Z. 11 Z. 12 Z. 13 Z. 14 Z. 15 Z. 16 Z. 17 Z. 18 Z. 19 Z. 20 Z. 21 Z. 22 Z. 23
80
90
100
110
120
130
140
Z. 8
Z. 9 Z. 10 Z. 11 Z. 12 Z. 13 Z. 14 Z. 15 Z. 16 Z. 17 Z. 18 Z. 19 Z. 20 Z. 21 Z. 22 Z. 23
81
91
101
111
121
131
141
150
160
170 180
190
200
210
151
161
171
181
191
201
211
24
220
230
0
221
231
241
33