Electrical Wiring
(B) Definition and description of SW03
SW 0 3 1
Address
setting mode
Code-set
SW03 2
indoor unit
address and
centralized
SW03 8
controller
address
(Note 2)
Note*:
Set the address by code when connecting the centralized controller or gateway or charge system.
Address of the centralized controller=communication address+0 or +64.
SW03_ 2=OFF, address of the centralized controller=communication address+0=communication address
SW03_ 2=ON, address of the centralized controller=communication address+64 (applies when the centralized controller is
used and there are more than 64 indoor units).
To use with 0010451181A in use, using code for address setting is required. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7, and SW03_ 8 are address codes that are set according
to the actual address.
The address-setting function of the wired controller for ultrathin card machines is disenabled.
0
Automatic address setting or wired controller address setting (default)
1
2
3
4
5
6
7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
...
...
...
...
...
...
0
1
1
1
1
1
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
1
...
...
...
...
...
.. .
1
1
1
1
1
1
Code-set address
8
Address of
indoor unit
0
0#
(Default)
1
1#
0
2#
...
...
1
63#
0
0#
1
1#
0
2#
.. .
...
1
63#
28
21
Address of
centralized controller
0#
(Default)
1#
2#
....
63#
64#
65#
66#
...
127#