1. Knock out the fresh air intake hole at the top panel.
2. Assemble the axial fan, fresh air adapter, fi lter and dust hose as shown in fi gure below.
ASSY. FRESH AIR ADAPTER
FILTER FRESH AIR INTAKE
3. The axial fan model are as follow.
a. ebm axial fan.
8556A - pin type.
b. ebm axial fan.
8556N - wire type.
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to
the smooth air fl ow. Please follow the installation clearance shown in the fi gures below. Select the coolest possible place
where intake air temperature is not greater than the outside air temperature.
Where a wall or other obstacle is in the path of outdoor unitʼs intake or exhaust airfl ow, follow the installation guidelines
below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
5SLY15D/DR and 5SLY20/25C/CR
Wall facing one side
More than 50
Side view
All manuals and user guides at all-guides.com
INSTALLATION OF FRESH AIR INTAKE
TOP PANEL
2" DUCT HOSE

INSTALLATION OF THE OUTDOOR UNIT

More than 100
More than 50
1-10
Wall facing two sides
More than 100
More than 150
Top view
Wall facing three sides
More than 150
More than 300
More than 50
Top view
More than 50
Unit: mm