Dimension
5CEY15/20/25E/ER
5CEY28ER
Please ensure that the following steps are taken:
•
Unit installation should be fi lted at least 10mm as recommended in Figure B.
•
The drain pipe slope shall be kept at least 1:100.
•
Provide clearance for easy servicing and optimal air fl ow as shown in Figure C.
•
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
•
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Figure C
Nut
Washer
Washer
Nut
400mm or more
All manuals and user guides at all-guides.com
A
B
C
1073
534
268
Hanger Bracket
Floor Standing Type
1-6
D
E
F
135
336
630
Ceiling
Indoor Unit
Drainage Pipe
250mm or less
Utensils, furnitures or built-in
architectural features must not
protrude more than 250 mm
Floor
300mm
(Min.)
1m or more
G
H
145
485