Dimension
5CEY15/20/25E/ER
5CEY28ER
Please ensure that the following steps are taken:
Unit installation should be fi lted at least 10mm as recommended in Figure B.
The drain pipe slope shall be kept at least 1:100.
Provide clearance for easy servicing and optimal air fl ow as shown in Figure C.
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Figure C
Nut
Washer
Washer
Nut
400mm or more
All manuals and user guides at all-guides.com
A
B
C
1073
534
268
Hanger Bracket
Floor Standing Type
1-6
D
E
F
135
336
630
Ceiling
Indoor Unit
Drainage Pipe
250mm or less
Utensils, furnitures or built-in
architectural features must not
protrude more than 250 mm
Floor
300mm
(Min.)
1m or more
G
H
145
485