PRODUCT DESCRIPTION
Specifications
PRODUCT DESCRIPTION
This condensate pump automatically removes condensate water that drips from an air conditioner evapora-
tor coil, refrigeration equipment coil, condensing furnace, or condensing boiler.
The pump is controlled by a float switch mechanism, which starts and stops the
pump automatically at factory preset levels.
S
Pumps with an
in the model number also include an auxiliary high-water level
switch. This switch is to be connected to a Low Voltage Class II circuit (e.g. thermo-
stat, alarm, or relay). The switch is delivered from the factory configured to open a
thermostat circuit in the event of high water level in the pump reservoir. Opening the
thermostat circuit interrupts the operation of the heating/cooling system thereby
stopping production of condensate. Alternatively, this switch can be reconfigured by
the installer to close a circuit in the event of high water level which operates an
external component (alarm or relay, purchased separately).
Pumps with a
T
in the model number also include a coil of 3/8" ID x 20' of vinyl tubing for use as discharge
tubing.
This product has been carefully tested, inspected, and packaged to ensure safe delivery and operation.
Please examine your item(s) carefully to ensure that no damage occurred during shipment. If damage has
occurred, please contact the place of purchase. They will assist you in replacement or repair, if required.
Specifications
Model Series
VCMA-15
VCMA-20
VCMA-20
Flow Rates
Model Series
VCMA-15
VCMA-20
VCMA-20
4
Volts
HZ
115
60
115
60
230
50/60
Volts
1' (0.3 m)
115
65 (246)
115
80 (303)
230
80 (303)
Amps
Watts
1.0
60
1.5
93
0.5
75
Performance GPH (LPH)
5' (1.5 m)
10' (3 m)
50 (190)
25 (95)
70 (265)
48 (182)
70 (265)
48 (182)
Weight
Weight with Tubing
4.4 lb. (2 kg)
5.8 lb. (2.6 kg)
5 lb. (2.3 kg)
6.3 lb. (2.9 kg)
5 lb. (2.3 kg)
6.3 lb. (2.9 kg)
Shut Off
15' (4.6 m)
0
15' (4.6 m)
25 (95)
20' (6.1 m)
25 (95)
17' (5.2 m)
PSI
6.5
8.7
7.4