MOUNTING INSTRUCTIONS BSR KIT 140/300
ENGLISH
ENGLISH
ENGLISH
-
-
-
The BSR safety block system is an automatism
that, when coupled to the J4C multi voltage
electric actuators, lets the valve situate in a
preferable position NC or NO, when there is a
power supply failure. Inside of the housing
there are a BSR print circuit board and a battery
pack, which is kept in continuous charge.
In case of the valve is not in the preferable
position and there is a power supply cut, the
BSR system returns the valve back to the
preferable position by means of the batteries
tension, operating as a "single acting" actuator.
VERY IMPORTANT:
PLEASE, FOLLOW THESE INSTRUCTIONS STEP BY STEP.IF THE CONNECTOR OF THE BATTERY PACK IS
PLUGED TO THE "BSR" PCB, BEFORE ARRIVING TO POINT 4, THE PCB COULD BE DAMAGED.
KIT COMPONENTS
A
1 BSR PCB.
B
2 Battery support.
C
2 Battery pack.
D
3 Sheet metal Fixing screws
E
1 Plastic clamp
1. Remove the hand wheel screw and take it off. (Fig. 1A & 1B).
2. Remove the 8 screws between the cover and the body of the actuator. (Fig. 2).
3. Carefully remove the cover, in order to install the kit. (Fig. 3).
4. Take the BSR PCB (A) from the KIT and connect it to the actuator PCB, by using the connector shown
in the picture. See (Fig.4). Fix it to the actuator metal plate, by using the Sheet metal fixing screw (D).
See (Fig.5).
5. Place the 2 battery packs (C) as per picture (Fig. 6A & 6B).
BSR 140/300
OUTSIDE BOX
A
B
INSIDE BOX
C
D
E
02