Cover plate
Cover
Figure 17
g.
Only connect the power supply cable once the entire installation of the air conditioner has been
completed.
G
TAKE CARE
For models with a capacity < 4.5 kW plug the plug into a wall socket.
For models with a capacity > 4.5 kW connect the power supply cable directly the power source.
Do not use a plug and socket as the high current can damage both the terminals of the plug and
the socket and even cause a fire.
Outdoor unit
Control cover
Screw
Figure 18
11.2 Connecting the electrical cables for the S42xx & S52xx(B) & SJA2519
models.
a.
Connect the cable to the indoor unit
b.
Indoor/Outdoor connection cable should be H07RN-F type, 2,5 mm².
c.
To mount the cable to the interior unit: Remove the front panel and the cover plate of the terminal
strip on the right hand side of the interior unit. Figure 19.
Front Panel
Front panel
Figure 19
4
78
78
Outdoor unit
L
N
S
or
To indoor unit
Electronic box
Cover plate
cover
L
N
S
'click'
Plug connector
Secure the cable with cord clamp