• Delivery with 2 equally long loose sensors. Delivery with one integrated and one loose
temperature sensor up to qp 6 m³/h.
• The radio function can be activated by Techem software.
• Due date programmed ex-works: 31.12 can be changed by Techem software.
Adjustable device properties when commissioning:
• Installation location of the volume measuring section in the inlet (
(see display).
!
The installation location may only be re-programmed during commissioning. The
table below is valid as a locking condition. Afterwards, the device properties can
no longer be changed.
[m³/h]
qp 0.6-2.5
qp 3.5-10
qp 15-600
Ambient conditions
Installation
• Electrical and magnetic fields can disturb electronic components in the energy meter.
Ensure sufficient distance (approx. 10cm) between the computer unit and possible
electromagnetic sources (e.g. transformers, electrical motors, etc.).
• Select a dry, easily accessible location.
• In non-condensing environments (except for volume measuring section for cold meas-
urement).
• In closed rooms.
• Not suitable for drinking water applications
Operating conditions
• Flow sensor protection class
• Ambient temperature
• Medium temperature (heat meter)
Storage conditions:
• Ambient temperatures
Radio (if activated)
• Transmission frequency: 868.95 MHz; transmission power: < 25 mW
Installation
General installation instructions
• Observe the environmental conditions!
• Do not carry out any welding, soldering or drilling work in the vicinity of the meter.
• Only install meters in operational systems.
• The volume measuring section must be protected against magnetite and dirt for the
device's entire working life. A strainer is recommended.
18
Installation location changea-
ble until Energy progress...
10 kWh
0.1 MWh
1 MWh
IP 54
Θ: +5 °C...55 °C
Θ: +5 °C...130 °C
Θ:
-25 °C...70 °C
Installation location changea-
ble until Energy progress...
4
) or in the outlet (
0.036 GJ
0.36 GJ
3.6 GJ
)